Date:05-15-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:4010301SYSTEM NAME:HEARST MEMORIAL STATE BEACHCOUNTY:SAN LUIS OBISPO 
SOURCE NO.:All SourcesSOURCE NAME:N/ASOURCE CLASS:N/ASTATUS:N/A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA4010301_001_001 SECONDARY/GP-202503 1928 ALKALINITY, BICARBONATE 330.000 10.000 MG/L 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1919 CALCIUM 90.000 1.000 MG/L 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1929 ALKALINITY, CARBONATE < 10.000 MG/L 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1017 CHLORIDE 177.000 1.000 MG/L 500 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202604 1905 COLOR 12.000 5.000 UNITS 15 04-04-2023 36 2026/04
CA4010301_001_001 SECONDARY/GP-202503 1022 COPPER, FREE < 50.000 UG/L 1000 50 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 2905 FOAMING AGENTS (SURFACTANTS) < 0.050 MG/L .5 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1915 HARDNESS, TOTAL (AS CACO3) 476.000 1.000 MG/L 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1021 HYDROXIDE AS CALCIUM CARBONATE < 10.000 MG/L 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202407 1028 IRON 1710.000 30.000 UG/L 300 100 04-16-2024 3 2024/07
CA4010301_001_001 SECONDARY/GP-202503 1031 MAGNESIUM 61.000 1.000 MG/L 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202407 1032 MANGANESE 640.000 10.000 UG/L 50 20 04-16-2024 3 2024/07
CA4010301_001_001 SECONDARY/GP-202604 1920 ODOR < 1.000 TON 3 1 04-04-2023 36 2026/04
CA4010301_001_001 SECONDARY/GP-202503 1925 PH 8.000 pH 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1050 SILVER < 10.000 UG/L 100 10 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1052 SODIUM 60.000 1.000 MG/L 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1064 CONDUCTIVITY @ 25 C UMHOS/CM 1150.000 UMHO/CM 1600 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1055 SULFATE 37.500 0.500 MG/L 500 .5 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202503 1930 TDS 610.000 40.000 MG/L 1000 03-15-2022 36 2025/03
CA4010301_001_001 SECONDARY/GP-202604 0100 TURBIDITY 3.900 0.100 NTU 5 .1 04-04-2023 36 2026/04
CA4010301_001_001 SECONDARY/GP-202503 1095 ZINC < 50.000 UG/L 5000 50 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1002 ALUMINUM < 50.000 UG/L 1000 50 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1005 ARSENIC 3.000 2.000 UG/L 10 2 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1010 BARIUM 159.000 100.000 UG/L 1000 100 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1015 CADMIUM < 1.000 UG/L 5 1 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1020 CHROMIUM < 10.000 UG/L 50 10 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1025 FLUORIDE 0.100 0.100 MG/L 2 .1 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1035 MERCURY < 1.000 UG/L 2 1 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1036 NICKEL < 10.000 UG/L 100 10 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1045 SELENIUM < 5.000 UG/L 50 5 03-15-2022 36 2025/03
CA4010301_001_001 INORGANIC-202503 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 03-15-2022 36 2025/03
CA4010301_001_001 NITRATE/NITRITE-202411 1040 NITRATE < 0.400 MG/L 10 .4 11-14-2023 12 2024/11
CA4010301_001_001 NITRATE/NITRITE-202503 1041 NITRITE < 0.400 MG/L 1 .4 03-15-2022 36 2025/03
CA4010301_002_002 SECONDARY/GP-202405 1028 IRON < 30.000 UG/L 300 100 04-16-2024 1 2024/05 DUE NOW
CA4010301_002_002 SECONDARY/GP-202405 1032 MANGANESE < 10.000 UG/L 50 20 04-16-2024 1 2024/05 DUE NOW
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.